First, I would like to say that the term "Buchholz Relay" is specific to a product by the Buchholz company. A more generic term would be a "gas accumulation relay," although the term Buchholz relay is commonly used in the power distribution industry. Secondly, a Buchholz relay is NOT the same as a sudden pressure relay (also known as a pressure rise relay). Sudden pressure relays are commonly used in liquid-filled transformers which do not have conservators (Sealed Tank Transformers), but they do serve a similar purpose, which is to alert the transformer owner to an abnormal pressure which is normally attributed to an electrical short inside the transformer. Does anyone else agree to editting this page to be more accurate? Phantomspeed 03:45, 9 August 2006 (UTC)Reply

Go for it. Citations be nice. I just had a quick look at IEEE Std. 100 and it's not defined there - I had thought this would be a genericized trademark. Logically the main article would be something like gas relay which could talk about both sudden pressure rise and slow accumulation, and then Buchholz relay would become a redirect to that - where we'd mention this name as sometimes used synonymously. --Wtshymanski 17:51, 9 August 2006 (UTC)Reply
OK, I will talk with my colleges and see if I can find an accurate source substanciating my claims. BTW, I am a professional mechanical transformer designer that works for a medium sized company producing medium sized (typically 500-50,000 kVA) oil and dry-type transformers.--Phantomspeed 02:52, 11 August 2006 (UTC)Reply

float operated switch, pressure relay edit

Modern Buchholz relais have a second float operated switch at a lower level which operates the circuit breakers too. They switch off the transformer before air can get into the active part and so cause an arc in an oil-air mixture which will end in a serious explosion.

It turned out, that it lasts too long until te oil starts moving when an arc occurs in a large transformer. Therefore it makes sense to equip large transformers with pressure operated relais anyway. —Preceding unsigned comment added by 62.47.133.41 (talk) 17:25, 9 December 2007 (UTC)Reply

Both external links are broken —Preceding unsigned comment added by 24.176.167.241 (talk) 20:06, 14 January 2011 (UTC)Reply

External links modified edit

Hello fellow Wikipedians,

I have just modified one external link on Buchholz relay. Please take a moment to review my edit. If you have any questions, or need the bot to ignore the links, or the page altogether, please visit this simple FaQ for additional information. I made the following changes:

When you have finished reviewing my changes, please set the checked parameter below to true or failed to let others know (documentation at {{Sourcecheck}}).

This message was posted before February 2018. After February 2018, "External links modified" talk page sections are no longer generated or monitored by InternetArchiveBot. No special action is required regarding these talk page notices, other than regular verification using the archive tool instructions below. Editors have permission to delete these "External links modified" talk page sections if they want to de-clutter talk pages, but see the RfC before doing mass systematic removals. This message is updated dynamically through the template {{source check}} (last update: 18 January 2022).

  • If you have discovered URLs which were erroneously considered dead by the bot, you can report them with this tool.
  • If you found an error with any archives or the URLs themselves, you can fix them with this tool.

Cheers.—InternetArchiveBot (Report bug) 03:06, 10 November 2016 (UTC)Reply